Damage Analysis of Elbow Fitting at Condenser Air Conditioning Cooling System

Authors

  • Hari Prastowo Institut Teknologi Sepuluh Nopember
  • Irfan Syarief Arief Institut Teknologi Sepuluh Nopember
  • Hamzah Fansyuri Institut Teknologi Sepuluh Nopember

DOI:

https://doi.org/10.12962/j25481479.v1i4.6163

Keywords:

Computational Fluid Dynamic (CFD), Erosion Corrotion, Flow Velocity, Vortex Generator

Abstract

Elbow fittings is one type of fitting on the piping installation that serves to change the flow direction. With the sudden flow of changes, it will affect the physical condition of the elbow. The flow changes in the elbow will result in changes of flow velocity that affect wall of elbow, the condition will cause erosion corrosion phenomenon. Erosion corrotion is a type of corrosion that uses a mechanical process through the relative movement of the flow and metal. Corrosion erosion can also be caused by impingment corrotion or very rapid flow movement. This study aims to determine the cause of damage elbow by using a CFD simulation and troubleshooting by adding a Vortex Generator or a installed disturber system in the pipeline installation and simulating it again. From the results of research conducted that elbow damage caused by high flow velocity that concerns the outer elbow. The addition of Vortex Generator is proven to be used to reduce excessive flow velocity on erosion-corroded parts. According to the results of the investigation the placement of the most efficient vortex generator if placed at a distance of 0.1 R from elbow inlet.

Downloads

Download data is not yet available.

Downloads

Published

2025-07-10

How to Cite

Prastowo, H., Arief, I. S., & Fansyuri, H. (2025). Damage Analysis of Elbow Fitting at Condenser Air Conditioning Cooling System. nternational ournal of arine ngineering nnovation and esearch, 1(4), 250–260. https://doi.org/10.12962/j25481479.v1i4.6163

Issue

Section

Articles

Most read articles by the same author(s)

1 2 > >>