Evaluation of Damage and Strengthening Recommendations A Case Study of the Lontar Badminton Sports Hall
Main Article Content
Abstract
An evaluation and recommendations for structural strengthening of the Lontar Badminton Sports Hall were carried out to analyze the structural adequacy following damage to the strauss piles and collapse of the retaining wall. Evaluation methods included an initial survey, destructive and non-destructive testing of structural elements, and structural analysis. Based on the analysis, several steel elements have a capacity ratio exceeding 1.0, indicating they cannot bear the design loads, while the steel profile connections still meet requirements. The reinforced concrete floor slabs are unable to withstand existing loads due to excessive spanning area. Similarly, the footings lack adequate dimensions and reinforcement due to the absence of foundations in that section. The lower structure, including pile caps and strauss piles, also fails to meet requirements as the concrete compressive strength is insufficient. This study recommends structural reinforcement through changes to the structural configuration of both the upper and lower structures.